Self-shielding at voltages through 345 KV by the flexible elements which serve as corona rings. Normally furnished without hardware shields. The 4-inch allowable movement accommodates 130 feet of aluminum bus over a 200°F temperature range.
Catalog Number | Pipe Size | . of Cables | Current | A | B | C | T | X | Weight |
---|---|---|---|---|---|---|---|---|---|
WFCCV-58-4B | 2 NPS | 4 | 2000 A | 12 | 17-1/2 | 24 | 3/4 | 3-1/2 | 13.10 |
WFCCV-58H-4B | 2 EHPS | 4 | 2000 A | 12 | 17-1/2 | 24 | 3/4 | 3-1/2 | 13.10 |
WFCCV-60-4B | 2-1/2 NPS | 4 | 2400 A | 12 | 17-1/2 | 25 | 3/4 | 3-1/2 | 15.10 |
WFCCV-60H-4B | 2-1/2 EHPS | 4 | 2400 A | 12 | 17-1/2 | 25 | 3/4 | 3-1/2 | 15.10 |
WFCCV-62-4B | 3 NPS | 4 | 2400 A | 12 | 17-1/2 | 26 | 3/4 | 3-1/2 | 14.80 |
WFCCV-62H-4B | 3 EHPS | 4 | 2400 A | 12 | 17-1/2 | 26 | 3/4 | 3-1/2 | 14.80 |
WFCCV-63-4B | 3-1/2 NPS | 4 | 2700 A | 12-1/2 | 18-1/2 | 26 | 1 | 4 | 16.55 |
WFCCV-63H-4B | 3-1/2 EHPS | 4 | 2700 A | 12-1/2 | 18-1/2 | 26 | 1 | 4 | 16.55 |
WFCCV-64-4B | 4 NPS | 4 | 3000 A | 12-1/2 | 18-3/4 | 27 | 1 | 4 | 16.80 |
WFCCV-64H-4B | 4 EHPS | 4 | 3000 A | 12-1/2 | 18-3/4 | 27 | 1 | 4 | 16.80 |
WFCCV-67-4B | 5 NPS | 6 | 4000 A | 18-1/2 | 24-1/2 | 32 | 1-1/8 | 4 | 31.40 |
WFCCV-67H-4B | 5 EHPS | 6 | 4000 A | 18-1/2 | 24-1/2 | 32 | 1-1/8 | 4 | 31.40 |
WFCCV-69-4B | 6 NPS | 6 | 4000 A | 21 | 27 | 33 | 1-1/8 | 4 | 33.70 |
WFCCV-69H-4B | 6 EHPS | 6 | 4000 A | 21 | 27 | 33 | 1-1/8 | 4 | 33.70 |